|
Table I Vertical Plaster Nominal
Thickness
Table II Horizontal Plaster
Nominal Thickness
A. The plaster thickness
is measured from the face of the substrate. For soffits,
the plaster thickness is measured from back of expanded
metal lath (exclusive of rib).
B. Sheathed framed construction
is recommended rather than open-frame construction.
The thickness of the cement plaster for these two types
of construction would be the same.
C. Basic stucco system
refers to a stucco assembly with lath.
D. An accepted and recommended
application of the basecoat is the double-back method,
which is the process of successive coats with little
or no delay.
E. Basic stucco system
should have a minimum thickness of 3/4 inches (19 mm),
which can include a 1/8-inch (3 mm) stucco finish coat.
F. If a fire-resistance
assembly is required, the minimum thickness of cement
plaster must be 7/8 inch (23 mm), which can include
a 1/8-inch (3-mm) stucco finish coat. If the finish
is an acrylic finish coat or some other approved coating,
the basecoat of cement plaster must be a minimum thickness
of 7/8 inch (23 mm).
Note: Plaster thickness
should conform to the applicable building codes.
G. Stucco finish coat
directly over concrete is also referred to as a skim
coat.
H. It is recommended
that a liquid bonding agent be applied to concrete before
the application of a direct cement plaster basecoat
or stucco finish coat.
I. The soffit framing
construction options for the basic stucco system are:
1) direct to a joist
system
2) suspended system
3) furring/sheathing
system
J. Direct-applied cement
plaster to a concrete or concrete masonry surface that
exceeds the maximum thickness requires self-furring
lath.
|